基于調(diào)制解調(diào)器與VB的PLC遠(yuǎn)程通訊系統(tǒng)設(shè)計(jì)
二.讀數(shù)寫數(shù)
本系統(tǒng)操作PLC的關(guān)鍵數(shù)據(jù)主要是水位的設(shè)定值PV=R0和當(dāng)前值CV=R1,即要對(duì)暫存器R0進(jìn)行寫操作,R1進(jìn)行讀操作;
依照協(xié)議VB設(shè)計(jì)的通訊程序必須指定一個(gè)命令碼,向PLC請(qǐng)求數(shù)據(jù)讀取,查的該命令碼為“46”,解釋為:連續(xù)多個(gè)緩存器之?dāng)?shù)據(jù)讀取。讀取R1的PC命令的ASCII碼寫法為:
“STX+ 01(站號(hào))+46(命令碼)+01(連續(xù)數(shù)據(jù)個(gè)數(shù))+R00001(數(shù)據(jù)開始地址)+LRC(偵誤值)+ETX”
依照協(xié)議VB設(shè)計(jì)的通訊程序必須指定一個(gè)命令碼,對(duì)PLC緩存器數(shù)據(jù)寫入,查的該命令碼為“47”,解釋為:連續(xù)多個(gè)緩存器之?dāng)?shù)據(jù)寫入。寫入R0的PC命令的ASCII碼寫法為:
“STX+ 01(站號(hào))+47(命令碼)+01(連續(xù)數(shù)據(jù)個(gè)數(shù))+R00000(數(shù)據(jù)開始地址)+XXXX(寫入的數(shù)據(jù)資料,16進(jìn)制)+LRC(偵誤值)+ETX”
讀取當(dāng)前值CV=R1,程序如下
Private Sub Timer1_Timer()
MSComm1.Output= Chr(2)+ “014601R00001”+ Lrc(“014601R00001”)+Chr(3)
Delay (10) ‘延時(shí)
CV = Val(“&H” + Mid(MSComm1.bbbbb, 7, 4)) ’數(shù)據(jù)處理,R0放于CV
CV.Text = CV
End Sub
寫入設(shè)定值PV=R0,程序如下
Private Sub Command1_Click()
If Len(Hex(PV.Text)) = 4 Then PV = Hex(PV.Text)
If Len(Hex(PV.Text)) = 3 Then PV = “0” + Hex(PV.Text
If Len(Hex(PV.Text)) = 2 Then PV = “00” + Hex(PV.Text)
If Len(Hex(PV.Text)) = 1 Then PV = “000” + Hex(PV.Text) ‘10進(jìn)制轉(zhuǎn)換16進(jìn)制
MSComm1.Output=Chr(2)+ “014701R00000”+ PV + +Lrc(“014701R00000” & PV)+Chr(3)
End Sub
三.偵誤值(CHECKSUM)計(jì)算
為VB的編程方便,把該計(jì)算做成單獨(dú)一個(gè)子程序,依所有數(shù)據(jù)累加,舍棄進(jìn)位的規(guī)則VB的LRC編程如下:
Private Function Lrc(Dats) As bbbbbb
Dim i
Dim Sum
Sum =2
For i = 1 To Len(Dats)
Sum = Sum + Asc(Mid(Dats, i, 1))
Next i
Lrc = Right(“0” + Hex(Sum + 2), 2)
End Function
5結(jié)束語
采用基于MODEM通訊的設(shè)計(jì)極方便地實(shí)現(xiàn)該小電站生廠調(diào)度,在這種只需短時(shí)間連接控制的系統(tǒng)應(yīng)用上可以大幅度地減小通訊成本,具有一定的推廣價(jià)值。另外,通過MODEM的連接,利用永宏編程軟件可以實(shí)現(xiàn)該設(shè)備的遠(yuǎn)程程序調(diào)試修改,通過兩個(gè)MODEM還可以實(shí)現(xiàn)兩臺(tái)遠(yuǎn)程PLC的CPU連接通訊等。